ESP AI Assistant

⏳ Please wait… analyzing your question & attachments (ESP-only)…
AI Well Screen
IPR Chart
Method: Vogel Units: psi / stb/d Pb fixed: 2660 psi
Pump Performance
SIM Auto Freq - + Hz: 50.0
3D Impeller (rotates with frequency)
Pump Curve + System + Operating Point
Data Transmission
Streaming trends (1 Hz)
Trends
Quick Reports
Auto-generated events
TimeTypeMessageSource
8.Accessories and Optimal Equipments

In almost every submersible installation we use three-phase power to run the down hole motors and you add the three transformers KVA together to get the total full load capability.

• KVA = (SV x NPA x 1.732) / 1000

• Let’s assume that we have a 225-HP, 57-amp motor with a required surface voltage of 2617 volts. Then:

KVA = (2617 x 57 x 1.732) / 1000 = 258

• Now we want to size our transformers equal to or greater than the required KVA.

• Never undersize the transformer bank because you can burn up the transformers and motor.

• The WG ESP catalog has a listing of transformers (reference Figure 6.2).

• Transformers come only in standard sizes.